SIMATIC S7-300

CPU CPU 312C 1) CPU 313C 1) CPU 313-2 PtP CPU 313C-2 DP 1) CPU 314C-2 PtP CPU 314C-2 DP 1)
Dimension (mm)
80 x 125 x 130 120 x 125 x 130 120 x 125 x 130
Required front connector 1 x 40-pin 2 x 40-pin 1 x 40-pin 2 x 40-pin
Order No. group: 6ES7 312-5BE. 313-5BF. 313-6BF. 313-6CF. 314-6BG. 314-6CG.
Memory
RAM 32 KB 64 KB 96 KB
Instructions 10 K 21 K 32 K
Processing times
Bit operation 0,2 µs 0,1 µs 0,1 µs
Word operation/fixed-point./floating-point operat. 0,4/5/6 µs 0,2/2/3 µs 0,2/2/3 µs
Bit memories/timers/counters
Bit memory 128 bytes 256 bytes 256 bytes
S7 timers/counters 128/128 256/256 256/256
IEC timers/counters
Address areas
I/O (bytes) 1024/1024 1024/1024 1024/1024 1024/1024
Process I/O image 128/128 bytes 128/128 bytes 128/128 bytes 128/128 bytes
Digital channels (central) 266 1016 1008 1016
Analog channels (central) 64 253 248 253
Integrated functions
Counter (incremental enc.) 2 , 24 V/10 kHz 3 incr.enc., 24 V/30 lHz 4 incr.enc., 24 V/60 kHz
Pulse outputs (PCM) 2 channels, max. 2.5 kHz 3 channels, max. 2.5 kHz

4 channels, max. 2.5 kHz

Frequency measurement 2 channels, max. 10 kHz 2 channels, max. 30 kHz 2 channels, max. 60 kHz
Open-loop positioning     SPB for positioning 1 axis via 2 DO, AO
Integrated "Controlling" FB PID controller PID controller PID controller
Integrated I/O
Digital inputs 10 x 24V DC; all channels can be used for process interrupts 24 x 24V DC; all channels can be used for process interrupts 16 x 24V DC; all channels can be used for process interrupts 24 x 24V DC; all channels can be used for process interrupts
Digital outputs 6 x 24 V DC, 0.5 A 16 x 24 V DC, 0.5 A 16 x 24 V DC, 0.5 A 16 x 24 V DC, 0.5 A
Analog inputs   4: ± 10 V, 0..10 V, ± 20 mA, 0/4..20 mA; 1: 0..600 Ω, PT100     4: ± 10 V, 0..10 V, ± 20 mA, 0/4..20 mA; 1: 0..600 Ω, PT100
Analog output   2: ± 10 V, 0..10 V, ± 20 mA, 0/4..20 mA     2: ± 10 V, 0..10 V, ± 20 mA, 0/4..20 mA
DP interface
DP maser systems int./ CP 342-5 -/n -/n -/n ■/n -/n ■/n
DP slave        
PtP interface
Properties     RS485/422   RS485/422  
Protocol driver     3964 (R), RK512, ASCII   3964 (R), RK512, ASCII  

 

 

Automation consultancy

To discuss your industrial automation, instrumentation and controls related problem, or to arrange a site-visit

Call: 0300-5776703, or e-mail us at This email address is being protected from spambots. You need JavaScript enabled to view it.

Job Openings

We are hiring Automation Project Engineers, for details click here

Design Services

Native RTL SupportC&M Engineering will design your system to your requirements and hardware preferences. C&M''s automation experts can design, upgrade, customize and troubleshoot your system

Read More

Docs / Support

Docs / SupportIn addition to comprehensive documentations in PDF format, you also get AUTOCAD drawings and your control software's for back-up purposes.

Consultancy services

Easy to startWe offer technology, industry expertise and business process best practices that will enable you to empower your workforce and achieve breakthrough levels of customer satisfaction, organizational effectiveness, worker productivity, and profitability.

Free business joomla templates