Technical data for failsafe CPUs

SIMATIC S7-300

CPU CPU 315F-2 DP 1) CPU 315F-2 PN/DP CPU 317F-2 DP 1) CPU 317F-2 PN/DP

CPU 319F-3 PN/DP

Dimension (mm)
40 x 125 x 130 80 x 125 x 130 80 x 125 130 120 x 125 x 130
Order No. group: 6ES7 312-6FF. 315-2FH. 317-6FF. 317-2FK. 318-3FL
Memory
RAM 192 KB 256 KB 1 MB

1.4 MB

Instructions 36 K (F instr.) 50 K (F instr.) 20 K (F instructions) 280 K (F onstr.
Processing times
Bit operation 0,1µs 0,05µs 0,01 µs
Word operation 0,2µs 0,2µs 0,02µs
Fixed-point operation 2 µs 0.2 µs 0.02 µs
Floating-point operation 3 µs 1 µs 0.04 µs
Bit memories/timers/counters
Bit memory 2048 bytes 4096 bytes 8182 bytes
S7 timers/counters 256/256 512/512 2048/2048
IEC timers/counters
Address areas
I/O (bytes) 2048/2048 8192/8192 8192/8192 8192/8192
I/O Process image 128/128 bytes 256/256 bytes 2048/2048 bytes 2048/2048 bytes
Digital channels (central) 1024 1024 1024 1024
Analog channels (central) 256 256 256 256
DP interface
DP maser systems internally/CP ■/■ ■/■ ■/■
DP slave
PROFINET interface
PROFINET CBA    
PROFINET IO    
TCP/IP    
UDP    
ISO-on-TCP (RFC 1006)    
Web server    

 

 

Siemens S7-300 PLC

SIMATIC S7-300

A graded CPU range with a wide performance range is available for configuring the controller. Thanks to their high processing speed, the CPUs enable short machine cycle times. The narrow module width results in a compact controller design or a small control cabinet.

 

The CPUs are available from a width of only 40 mm. Fail-safe CPUs are available for safety-oriented applications. The PROFIsafe profile for safe communication via PROFIBUS and PROFINET allows the integration of safety-related functions into standard automation environments.

 

Compact CPUs with width of 80 or 120 mm also offer integral I/O and integral technological functions. This onboard I/O (digital/analog) and the technological functions save additional investments in other modules.

Applications include the following:

  • High-speed counting/measuring with direct access to the hardware counter
  • Simple positioning with direct control of the MICROMASTER frequency inverter
  • PID control with integral function block

 

This range is rounded off by a special technology CPU with powerful technological function, especially for motion control.

 

Together with the integral digital I/O and equidistant and isochronous mode on PROFIBUS DP, off-the-shelf, PLCopen-compliant motion control of several (even linked) axes.

 

Micro Memory Card

 

 

The Micro Memory card is a compact medium that meets the highest industrial requirements, especially ESD protection and mechanical ruggedness.

 

The system-tested Micro Memory Card Allows more write cycles than conventional memory cards and offers know-how protection because the serial number can be read out.

 

Version CPU
Isochronous mode on the PROFIBUS
Integrated interfaces Integral I/O Integrated technological functions
Standard CPUs
  CPU 312, 314 1)   MPI    
CPU 315-2 DP 1)   MPI, DP
CPU 315-2 PN/DP 1)
DP/MPI, PORFINET
CPU 317-2 DP
DP/MPI, DP
CPU 317-2 PN/DP 1)
DP/MPI, PROFINET
  NEW CPU 319-3 PN/DP
DP/MPI, DP, PROFINET
Failsafe CPUs
  CPU 315F-2 DP 1)   MPI, DP   Fail satety with PROFIsafe profile
CPU 315F-2 PN/DP
DP/MPI, PROFINET
CPU 317F-2 DP 1)
DP/MPI, DP
CPU 317F-2 PN/DP
DP/MPI, PROFINET
CPU 319F-3 PN/DP
DP/MPI, DP, PROFINET
Compact CPUs
  CPU 312C 1)   MPI Digital Counting
Rules
Frequency measurement
Pulse width modulation
Pulse generator
CPU 313C 1)   MPI Digital, Analog
CPU 313C-2 PtP   MPI, PtP Digital
CPU 313C-2 DP 1)   MPI, DP Digital
CPU 314C-2 PtP 1)   MPI, PtP Digital, Analog

As above, and additionally
Positioning

CPU 314C-2 DP 1)   MPI, DP Digital, Analog
Technology CPUs
  CPU 315T-2 DP   DP/MPI, DP(DRIVE) Digital Synchronous operation
Traversing to fixed stop
Pressure mark correction
Cam control
Controlled positioning
CPU 317T-2DP   DP/MPI, DP(DRIVE) Digital

 

 

Technical specifications Compact CPUs

SIMATIC S7-300

CPU CPU 312C 1) CPU 313C 1) CPU 313-2 PtP CPU 313C-2 DP 1) CPU 314C-2 PtP CPU 314C-2 DP 1)
Dimension (mm)
80 x 125 x 130 120 x 125 x 130 120 x 125 x 130
Required front connector 1 x 40-pin 2 x 40-pin 1 x 40-pin 2 x 40-pin
Order No. group: 6ES7 312-5BE. 313-5BF. 313-6BF. 313-6CF. 314-6BG. 314-6CG.
Memory
RAM 32 KB 64 KB 96 KB
Instructions 10 K 21 K 32 K
Processing times
Bit operation 0,2 µs 0,1 µs 0,1 µs
Word operation/fixed-point./floating-point operat. 0,4/5/6 µs 0,2/2/3 µs 0,2/2/3 µs
Bit memories/timers/counters
Bit memory 128 bytes 256 bytes 256 bytes
S7 timers/counters 128/128 256/256 256/256
IEC timers/counters
Address areas
I/O (bytes) 1024/1024 1024/1024 1024/1024 1024/1024
Process I/O image 128/128 bytes 128/128 bytes 128/128 bytes 128/128 bytes
Digital channels (central) 266 1016 1008 1016
Analog channels (central) 64 253 248 253
Integrated functions
Counter (incremental enc.) 2 , 24 V/10 kHz 3 incr.enc., 24 V/30 lHz 4 incr.enc., 24 V/60 kHz
Pulse outputs (PCM) 2 channels, max. 2.5 kHz 3 channels, max. 2.5 kHz

4 channels, max. 2.5 kHz

Frequency measurement 2 channels, max. 10 kHz 2 channels, max. 30 kHz 2 channels, max. 60 kHz
Open-loop positioning     SPB for positioning 1 axis via 2 DO, AO
Integrated "Controlling" FB PID controller PID controller PID controller
Integrated I/O
Digital inputs 10 x 24V DC; all channels can be used for process interrupts 24 x 24V DC; all channels can be used for process interrupts 16 x 24V DC; all channels can be used for process interrupts 24 x 24V DC; all channels can be used for process interrupts
Digital outputs 6 x 24 V DC, 0.5 A 16 x 24 V DC, 0.5 A 16 x 24 V DC, 0.5 A 16 x 24 V DC, 0.5 A
Analog inputs   4: ± 10 V, 0..10 V, ± 20 mA, 0/4..20 mA; 1: 0..600 Ω, PT100     4: ± 10 V, 0..10 V, ± 20 mA, 0/4..20 mA; 1: 0..600 Ω, PT100
Analog output   2: ± 10 V, 0..10 V, ± 20 mA, 0/4..20 mA     2: ± 10 V, 0..10 V, ± 20 mA, 0/4..20 mA
DP interface
DP maser systems int./ CP 342-5 -/n -/n -/n ■/n -/n ■/n
DP slave        
PtP interface
Properties     RS485/422   RS485/422  
Protocol driver     3964 (R), RK512, ASCII   3964 (R), RK512, ASCII  

 

 

Technical specifications Standard CPUs

SIMATIC S7-300

CPU CPU 312 CPU 314 1)
CPU 315-2 DP 1)
CPU 315-2 PN/DP 1) CPU 317-2 DP CPU 317-2 PN/DP 1) CPU 319-3 PN/DP
Dimension (mm)
40 x 125 x 130 40 x 125 x 130 80 x 125 x 130 80 x 125 x 130 120 x 125 x 130
Order No. group: 6ES7 312-1AE. 314-1AG. 315-2AG. 315-2EH. 317-2AJ. 317-2EK. 318-EL.
Memory
RAM 32 KB 96 KB 128 KB 256 KB 512 KB 1 MB 1.4 MB
Instructions 10 K 32 K 42 K 84 K 170 K 340 K 470 K
Processing times
Bit operation 0.2 µs 0.1 µs 0.1 µs 0.05 µs 0.01 µs
Word operation 0.4 µs 0.2 µs 0.2µs 0.2µs 0.02 µs
Fixed-point operation 5 µs 2 µs 2 µs 0.2 µs 0.02 µs
Floating-point operation 6 µs 3 µs 3 µs 1 µs 0.04 µs
Bit memories/times/counters
Bit memory 128 bytes 256 bytes 2048 bytes 4096 bytes 8192/8192
S7 timers/counters 128/128 256/256 256/256 512/512 2048/2048
IEC timers/ counters
Address areas
I/O (bytes) 1024/1024 1024/1024 2048/2048 8192/8192 8192/8192 8192/8192
I/O process image (bytes) 128/128 128/128 128/128 256/256 2048/2048 2048/2048
Digital channels (central) 256 1024 1024 1024 1024 1024
Analog channels (central) 64 256 256 256   256
DP interfaces
DP master system internal / CP 342-5 -/ ■/■ ■/■ ■/■ ■/■
DP slaves  
PROFINET interface
PROFINET CBA    
PROFINET IO    
TCP/IP    
UDP    
ISO-on-TCP (RFC 1006)     n
Web server     n

 

 

More Articles...


Warning: Illegal string offset 'active' in /home4/rehan/public_html/templates/jsn_epic_free/html/pagination.php on line 94

Warning: Illegal string offset 'active' in /home4/rehan/public_html/templates/jsn_epic_free/html/pagination.php on line 100

Warning: Illegal string offset 'active' in /home4/rehan/public_html/templates/jsn_epic_free/html/pagination.php on line 94

Warning: Illegal string offset 'active' in /home4/rehan/public_html/templates/jsn_epic_free/html/pagination.php on line 100

Warning: Illegal string offset 'active' in /home4/rehan/public_html/templates/jsn_epic_free/html/pagination.php on line 94

Warning: Illegal string offset 'active' in /home4/rehan/public_html/templates/jsn_epic_free/html/pagination.php on line 100

Page 2 of 3

Automation consultancy

To discuss your industrial automation, instrumentation and controls related problem, or to arrange a site-visit

Call: 0300-5776703, or e-mail us at This email address is being protected from spambots. You need JavaScript enabled to view it.

Job Openings

We are hiring Electrician/Technician, for details click here

Design Services

Native RTL SupportC&M Engineering will design your system to your requirements and hardware preferences. C&M''s automation experts can design, upgrade, customize and troubleshoot your system

Read More

Docs / Support

Docs / SupportIn addition to comprehensive documentations in PDF format, you also get AUTOCAD drawings and your control software's for back-up purposes.

Consultancy services

Easy to startWe offer technology, industry expertise and business process best practices that will enable you to empower your workforce and achieve breakthrough levels of customer satisfaction, organizational effectiveness, worker productivity, and profitability.

Free business joomla templates