Features
- Advanced instruction set based on PLC-5® controllers
- DH-485 port on SLC™ 5/01 controllers receive processor-to-processor communications and support programming
- Communication ports on SLC 5/02 through SLC 5/05 controllers can initiate messages
- SLC 5/02 through SLC 5/05 controllers support Universal Remote I/O or DeviceNet™ I/O, using a scanner module
- SLC BASIC (1747-BAS) module adds BASIC or C programming capability
Products
- 1747 SLC 500 Controllers
SLC 500 Controller Comparison
Controller Series | Instruction Memory Words | Max. I/O Points | I/O Options | Built-in Ports | Additional Features |
---|---|---|---|---|---|
SLC 5/01 | 1 K or 4 K | 960 | Local I/O | DH-485 (cannot initiate messages) | Basic set of 51 instructions |
SLC 5/02 | 4 K | 4096 | Local I/O, remote I/O | DH-485 | Expanded instruction set, faster scan times, extensive diagnostics for more complex applications |
SLC 5/03 | 8 K, 16 K, or 32 K | 4096 | Local I/O, remote I/O |
DH-485, RS-232-C (ASCII or DF1) |
Connects to external intelligent devices using the RS-232 port, without additional modules |
SLC 5/04 | 16 K, 32 K, or 64 K | 4096 | Local I/O, remote I/O |
DH+, RS-232-C (ASCII or DF1) |
High-speed peer-to-peer communications and direct connection to PLC-5 controllers |
SLC 5/05 | 16 K, 32 K, or 64 K | 4096 | Local I/O, remote I/O | Ethernet (10BASE-T 10/100 Mbps), RS-232-C(ASCII or DF1) | Ethernet supports program upload and download, on-line editing, and peer-to-peer messaging |
Certifications
- UL, C-UL, CE, C-Tick