For use within explosive plants
Description
In many branches there exist explosive environments in manufacturing and following processes.
To assure a preferably high level of safety in these areas, there exist conditions in terms of laws, orders and norms.
For the use in these areas, there are Ex modules that are endorsed intrinsically-safe sensors and actuators being in zone 1 or 2 of explosive plants.
Area of application
The Ex modules are available to the automation particularly of chemical plants as appropriate operating supplies. They are applicable for applications in the measurement-, control- and regulation technology.
Areas of application:
-
Chemical/petrochemical industry
-
Gas industry
-
Offshore industry
-
Transportation (e.g. tankers)
-
Automotive engineering (e.g. at varnishing)
-
Energy supply, energy distribution etc.
-
Generating plants
-
Special engineering (e.g. printing machines, cleaning machines)
Benefit
The igniting protection type intrinsically-safe offers following advantages to the user:
-
Easy interchangeability of intrinsically-safe equipment during the business
-
Easy measurement and calibration of the measuring section during the business
-
Working in intrinsically-safe energized loops without stop of the plant
-
No complex case execution (e.g. compression-proof encapsulation) necessary
-
Linking of intrinsically-safe equipment of different manufacturers possible
-
Approved igniting protection type in chemical industry
Design and functions
The main function of the analog Ex modules is the separation of the intrinsically-safe loops of the Ex field and the non intrinsically-safe internal loops of the automation plant.
The Ex analogl input modules transform the analog signals of the intrinsically-safe equipment in digital values for the following working.
The Ex analog output modules transform the digital signals of the automation plant in analog signals being necessary for the process.
Ex analog input/output modules are “appropriate electrical eqipment” of the igniting protection type intrinsically-safe (term [EEx ib] IIC according to DIN EN 50020). You get next to intrinsically-safe ones also non intrinsically-safe loops.
-
Same systems engineering as the other modules of S7-300
-
Galvanic separation of the module
-
Confusion safety through coding
-
Supply of the sensors and actuators through the module
-
Direct wiring of the inputs and outputs of the modules without a separating switch amplifier or transmitter feed unit
-
Different wiring of the software possible
-
Diagnosis capable modules
-
Reduced planning, installation and documentation effort
-
Operation also with ET 200M possible with connection to all SIMATIC automation systems and as norm slave to all PROFIBUS DP networks.
Technical specifications
Term |
Analog input |
Analog input |
Analog output |
Channels |
4 AI in 4 channel groups |
8AI in 4 channel groups, 8x thermocouples; 4x RTD-thermoresistors |
4 AO in 4 channel groups |
Certificates, admissions, norms |
|||
(igniting protection type according to EN 50020 (CENELEC) |
[EEx lib] IIC |
[EEx lib] IIC |
[EEx lib] IIC |
igniting protection type according to FM |
Class I, Division 2, Group A, B, C, D T4 Class I, Zone 2, Group IIC T4 |
Class I, Division 2, Group A, B, C, D T4 Class I, Zone 2, Group IIC T4 |
Class I, Division 2, Group A, B, C, D T4 |
Test number PTB |
Ex-96.D.2092X |
Ex-96.D.2108X |
Ex-96.D.2026X |
Term |
Analog input |
Analog input |
Channels |
2 AI in 2 channel groups |
2 AO in 2 channel groups |
igniting protection type according to EN 50020 (CENELEC) |
II3 (2) GEEx nA [lib] IIC T4 |
II3 (2) GEEx nA [lib] IIC T4 |
igniting protection type according to FM |
Class I, Division 2, Group A, B, C, D T4Class I, Zone 2, Group IIC T4 |
Class I, Division 2, Group A, B, C, D T4Class I, Zone 2, Group IIC T4 |
Test number PTB |
KEMA 97ATEX3039 X |
KEMA 97ATEX2359 X |