General Specifications

Type AC power supply models DC power supply models
Model CP1E-[][][]D[]-A CP1E-[][][]D[]-D
Enclosure Mounted in a panel
Dimensions (H × D × W) CPU Unit with 10 I/O points (CP1E-E10D[]-[]): 90mm *1 ×85mm *2 × 66 mm
CPU Unit with 14 or 20 I/O points (CP1E-[]14D[]-[]/[]20D[]-[]): 90mm *1 × 85mm *2 × 86 mm
CPU Unit with 30 I/O points (CP1E-[]30D[]-[]): 90mm *1 × 85mm *2 × 130 mm
CPU Unit with 40 I/O points (CP1E-[]40D[]-[]): 90mm *1 × 85mm *2 × 150 mm
CPU Unit with 60 I/O points (CP1E-N60D[]-[]): 90mm *1 ×85mm *2 × 195 mm
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D[]-[]): 90mm *1 ×85mm *2 × 130 mm
Weight CPU Unit with 10 I/O points (CP1E-E10D[]-[]): 300g max.
CPU Unit with 14 I/O points (CP1E-[]14D[]-[]): 360g max.
CPU Unit with 20 I/O points (CP1E-[]20D[]-[]): 370g max.
CPU Unit with 30 I/O points (CP1E-[]30D[]-[]): 600g max.
CPU Unit with 40 I/O points (CP1E-[]40D[]-[]): 660g max.
CPU Unit with 60 I/O points (CP1E-N60D[]-[]): 850g max.
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D[]-[]): 680g max.
Electrical
specifica-
tions
Supply voltage 100 to 240 VAC 50/60 Hz 24 VDC
Operating voltage
range
85 to 264 VAC 20.4 to 26.4 VDC
Power consumption 15 VA/100 VAC max.
25 VA/240 VAC max.
(CP1E-E10D[]-A/[]14D[]-A/[]20D[]-A)
9 W max. (CP1E-E10D[]-D)
13 W max. (CP1E-N14D[]-D/N20D[]-D)
50 VA/100 VAC max.
70 VA/240 VAC max.
(CP1E-NA20D[]-A/[]30D[]-A/[]40D[]-A/N60D[]-A)
20 W max.
(CP1E-NA20D[]-D/N30D[]-D/N40D[]-D/N60D[]-D) *4
Inrush current 120 VAC, 20 A for 8 ms max. for cold start at
room temperature
240 VAC, 40 A for 8 ms max. for cold start at
room temperature
24 VDC, 30 A for 20 ms max. for cold start at room
temperature
External power supply
*3
Not provided.
(CP1E-E10D[]-A/[]14D[]-A/[]20D[]-A)
24 VDC, 300 mA
(CP1E-NA20D[]-A/[]30D[]-A/[]40D[]-A/N60D[]-A)
Not provided
Insulation resistance 20 MΩ min. (at 500 VDC) between the external
AC terminals and GR terminals
Except between DC primary current and DC
secondary current
Dielectric strength 2,300 VAC 50/60Hz for 1 min between AC
external and GR terminals Leakage current:
5 mA max.
Except between DC primary current and DC
secondary current
Power OFF
detection time
10 ms min. 2 ms min.
Application
environ-
ment
Ambient operating
temperature
0 to 55 °C
Ambient humidity 10% to 90%
Atmosphere No corrosive gas.
Ambient storage
temperature
-20 to 75 °C (excluding battery)
Altitude 2,000 m max.
Pollution degree 2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise resistance 2 kV on power supply line (Conforms to IEC61000-4-4.)
Overvoltage category Category II: Conforms to JIS B3502 and IEC 61131-2.
EMC Immunity Level Zone B
Vibration resistance Conforms to JIS 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock resistance Conforms to JIS 60068-2-27.
147 m/s2, 3 times in X, Y, and Z directions
Terminal block Fixed (not removable)
Terminal screw size M3
Applicable standards Conforms to EC Directive
Grounding method Ground to 100 Ω or less.

*1.Total of 110 mm with mounting brackets.

*2.Excluding cables.

*3.Use the external power supply to power input devices. Do not use it to drive output devices.

*4.This is the rated value for the maximum system configuration. Use the following formula to calculate power consumption for CPU Units with DC power.
Formula: DC power consumption = (5V current consumption × 5 V/70% (internal power efficiency) + 24V current consumption) × 1.1(current fluctuation factor)
The above calculation results show that a DC power supply with a greater capacity is required.

Item CP1E-[][]D[]-[] CP1E-N[][]D[]-[]
CP1E-NA[][]D[]-[]
Program capacity 2 K steps (8 Kbytes) including the
symbol table, comments, and program
indices of the CX-Programmer
8 K steps (32 Kbytes) including the symbol table,
comments, and program indices of the CX-Programmer
Control method Stored program method
I/O control method Cyclic scan with immediate refreshing
Program language Ladder diagram
Instructions Approximately 200
Processing
speed
Overhead processing time 0.4 ms
Instruction execution times Basic instructions (LD): 1.19 µs min.
Special instructions (MOV): 7.9 µs min.
Number of CP1W-series Expansion Units
connected
CP1E-E10D[]-[]/[]14D[]-[]/[]20D[]-[]: None
CP1E-[]30D[]-[]/[]40D[]-[]/N60D[]-[]/NA20D[]-[]: 3 units
Maximum number of I/O points CP1E-E10D[]-[]: 10
CP1E-[]14D[]-[]: 14
CP1E-[]20D[]-[]: 20
CP1E-[]30D[]-[]: 150 (30 built in, 40 × 3 expansion)
CP1E-[]40D[]-[]: 160 (40 built in, 40 × 3 expansion)
CP1E-N60D[]-[]: 180 (60 built in, 40 × 3 expansion)
CP1E-NA20D[]-[]: 140 (20 built in, 40 × 3 expansion)
Built-in I/O CP1E-E10D[]-[]: 10 (6 inputs, 4 outputs)
CP1E-[]14D[]-[]: 14 (8 inputs, 6 outputs)
CP1E-[]20D[]-[]: 20 (12 inputs, 8 outputs)
CP1E-[]30D[]-[]: 30 (18 inputs, 12 outputs)
CP1E-[]40D[]-[]: 40 (24 inputs, 16 outputs)
CP1E-N60D[]-[]: 60 (36 inputs, 24 outputs)
CP1E-NA20D[]-[]: 20 (12 inputs, 8 outputs)
Built-in
input
functions
High-speed
counters
High-speed
counter mode/
maximum
frequency
Incremental Pulse Inputs
10 kHz:
6 counters
5 counters (only for 10 I/O points)
Up/Down Inputs
10 kHz: 2 counters
Pulse + Direction Inputs
10 kHz: 2 counters
Differential Phase Inputs (4x)
5 kHz: 2 counters
Incremental Pulse Inputs
100 kHz: 2 counters, 10 kHz: 4 counters
Up/Down Inputs
100 kHz: 1 counters, 10 kHz: 1 counters
Pulse + Direction Inputs
100 kHz: 2 counters
Differential Phase Inputs (4x)
50 kHz: 1 counter, 5 kHz: 1 counter
Counting mode Linear mode
Ring mode
Count value 32 bits
Counter reset
modes
Phase Z and software reset (excluding increment pulse input)
Software reset
Control method Target Matching
Range Comparison
Input interrupts 6 inputs (4 inputs only for 10 I/O points)
Interrupt input pulse width: 50 µs min.
Quick-response Inputs 6 inputs (4 inputs only for 10 I/O points)
Input pulse width: 50 µs min.
Normal input Input constants Delays can be set in the PLC Setup (0 to 32 ms, default: 8 ms).
Set values: 0, 1, 2, 4, 8, 16, or 32 ms
Built-in
output
functions
Pulse outputs
(Models with
transistor
outputs only)
Pulse output
method and
output
frequency
Pulse output function not included Pulse + Direction Mode
1 Hz to 100 kHz: 2 outputs
Output mode Continuous mode (for speed control)
Independent mode (for position control)
Number of
output pulses
elative coordinates: 0000 0000 to 7FFF FFFF hex
(0 to 2147483647)
Absolute coordinates: 8000 0000 to 7FFF FFFF hex
(-2147483647 to 2147483647)
Acceleration/
deceleration
curves
Trapezoidal acceleration and deceleration
(Cannot perform S-curve acceleration and
deceleration.)
Changing SVs
during
instruction
execution
Only target position can be changed.
Origin searches Included
Pulse outputs
(Models with
transistor
outputs only)
Frequency PWM output function not included 2.0 to 6,553.5 Hz (in increments of 0.1 Hz) with
1 output or 2 Hz to 32,000 Hz (in increments of
1 Hz) with 1 output
Duty factor 0.0% to 100.0% (in increments of 0.1%)
Accuracy: +1%/-0% at 2 Hz to 10,000 Hz and
+5%/-0% at 10,000 Hz to 32,000 kHz
Output mode Continuous Mode
Built-in analog Analog input Analog function not included Setting range: 0 to 6,000 (2 channels only for NA-type)
Analog output Setting range: 0 to 6,000 (1 channels only for NA-type)
Analog adjusters 2 adjusters (Setting range: 0 to 255)
Communi-
cations
B-type Peripheral USB Port Conforming to USB 2.0 B type connector
  Transmission
distance
5 m max.
Built-in RS-232C port No built-in RS-232C port Interface: Conforms to EIA RS-232C.
  Communications
method
Half duplex
synchronization Start-stop
Baud rate 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
Transmission
distance
15 m max.
Supported
protocol
Host Link
1:N NT Link
No-protocol mode
Serial PLC Links (master, slave)
Modbus-RTU Easy Master
Serial Option port Option Board cannot be mounted. 1 port (Option Board can be mounted only to
N30/40/60 and NA20 CPU Units.)
  Mountable
Option Boards
One RS-232C port: CP1W-CIF01
One RS-422A/485 port (not isolated): CP1W-CIF11
One RS-422A/485 port (isolated): CP1W-CIF12
One Ethernet port: CP1W-CIF41
Communications
method
Depends on Option Board.
synchronization Depends on Option Board.
Baud rate 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
Compatible
protocols
Host Link
1:N NT Link
No-protocol mode
Serial PLC Links (master, slave)
Modbus-RTU Easy Master
Number of tasks 17
One cyclic execution task
One scheduled interrupt task (always interrupt task 1)
Six input interrupt tasks (interrupt tasks 2 to 7)
Sixteen high-speed counter interrupt tasks (interrupt tasks 1 to 16)
Maximum subroutine number 128
Maximum jump number 128
Scheduled interrupt tasks 1 interrupt task
Clock Clock function not included.
The time of error occurrence displays
01-01-01 01:01:01 Sunday
Included.
Accuracy (monthly deviation):
-4.5 min to -0.5 min at ambient temperature of 55°C,
-2.0 min to +2.0 min at ambient temperature of 25°C,
-2.5 min to +1.5 min at ambient temperature of 0°C
Memory
backup
Built-in EEPROM Ladder programs and parameters are automatically saved to built-in EEPROM
A section of the Data Memory Area can be saved to the built-in EEPROM.
Battery backup With
CP1W-BAT01 Battery
(Sold separately)
Battery cannot be mounted. CP1W-BAT01 can be used.
Maximum battery service life: 5 years
Backup Time
Guaranteed value (ambient temperature: 55°C):
13,000 hours (approx. 1.5 years)
Effective value (ambient temperature: 25°C):
43,000 hours (approx. 5 years)
CIO Area Input Bits 1,600 bits (100 words): CIO 0.00 to CIO 99.15 (CIO 00 to CIO 99)
Output Bits 1,600 bits (100 words): CIO 100.00 to CIO 199.15 (CIO 100 to CIO 199)
Serial PLC Link Words 1,440 bits (90 words): CIO 200.00 to CIO 289.15 (words CIO 200 to CIO 289)
Work Area (W) 1,600 bits (100 words): W0.00 to W99.15 (W0 to W99)
Holding Area (H) 800 bits (50 words): H0.00 to H49.15 (H0 to H49)
Bits in this area maintain their ON/OFF status when operating mode is changed.
Auxiliary Area (A) Read-only: 7,168 bits (448 words) A0 to A447
Read/write: 4,896 bits (306 words) in words A448 to A753
Temporary Relay Area (TR) (TR Area) 16 bits: TR0 to TR15
Timer Area (T) 256 timer numbers (T0 to T255 (separate from counters))
Counter Area (C) 256 counter numbers (C0 to C255 (separate from timers))
Data Memory Area (D) 2 Kwords: D0 to D2047
Of these, 1,500 words can be saved to
the backup memory (built-in EEPROM)
using settings in the Auxiliary Area.
8 Kwords: D0 to D8191
Of these, 7,000 words can be saved to the backup
memory (built-in EEP-ROM) using settings in the
Auxiliary Area
Operating modes PROGRAM mode:
Program execution is stopped.
Preparations can be executed prior to program execution in this mode.
MONITOR mode:
Programs are executed.
Some operations, such as online editing, and changes to present values in I/O memory, are
enabled in this mode.
RUN mode:
Programs are executed.
This is the normal operating mode.