• Address

    C-188, Sector 31-D, P&T Society,

    Korangi Industrial Area,

    Karachi-74900,

    Pakistan

     

  • Call us on

     +92-21-35070751

     +92-300-5776703

  • Mail us @

    info@pakplc.com

     

Analog expansion board (A/D conversion, D/A conversion)

Model
(Number of channels)
Input specifications Applicable FX PLC
Item Input voltage Input current FX
3S
FX
3G
FX
3U
FX
3GC
FX
3UC
FX3G-2AD-BD
(Input 2 ch)
Input
range
0 to 10 V DC
(Input resistance 198.7 kΩ)
4 to 20 mA DC
(Input resistance 250 Ω)
*3

Max.
1 unit
*1*2

Max.
2 units
× × ×
Resolution 2.5 mV
(10 V/4000)
8 μA
{(20 - 4 mA)/2000}
FX3G-1DA-BD
(Output 1 ch)
Output
range
0 to 10 V DC
(External load resistance value
2 kΩ to 1 MΩ)
4 to 20 mA DC
(External load resistance value
500 Ω or less)
*3

Max.
1 unit
*1*2

Max.
2 units
× × ×
Resolution 2.5 mV
(10 V/4000)
8 μA
{(20 - 4 mA)/2000}

*1: Supported by FX3G ver. 1.10 and later.
*2: FX3G 14pt, 24pt models: 1 board. 40pt, 60pt models: 2 boards.
*3: Function expansion board and FX3S-CNV-ADP cannot be used together.

 

Mixed Analog Input/Output (A/D conversion, D/A conversion)

Model
(Number of channels)
Input/output specifications Applicable FX PLC
Item Input/output voltage Input/output current FX
3S
FX
3G
FX
3U
FX
3GC
FX
3UC
FX3U-3A-ADP
(Input 2 ch)
(Output 1ch)
Input
range
0 to 10 V DC
(Input resistance
198.7 kΩ)
4 to 20 mA DC
(Input resistance 250 Ω)
*7

Max.
1 unit
*1*6

Max.
2 units
*2

Max.
4 units

Max.
2 units
*3

Max.
4 units
Output
range
0 to 10 V DC
(External load resistance value
5 kΩ to 1 MΩ)
4 to 20 mA DC
(External load resistance value
500 Ω or less)
Resolution [Input voltage]
2.5 mV (10 V/4000)
[Output voltage]
2.5 mV (10 V/4000)
[Input current]
5 μA (16 mA/3200)
[Onput current]
4 μA (16 mA/4000)
FX2N-5A
(Input 4 ch)
(Output 1ch)
Input
range
-100 to 100 mV DC
-10 to 10 V DC
(Input resistance 200 kΩ)
-20 to 20 mA DC
4 to 20 mA DC
(Input resistance 250 Ω)
× ×
Max.
8 units
× *4*5

Max.
8 units
Output
range
-10 to 10 V DC
(External load resistance value
2 kΩ to 1 MΩ)
0 to 20 mA DC,
4 to 20 mA DC
(External load resistance value
500 Ω or less)
Resolution 50 μV
(at ±100 mV)
312.5 μV
(at ±10 V)
1.25 μA,10 μA
((depending on
mode used))

 

*1: Supported by FX3G ver.1.20 and later. For connection to FX3G, FX3G-CNV-ADP is required.
*2: Supported by FX3U ver.2.61 and later. For connection to FX3U, function expansion board is required.
*3: Supported by FX3UC ver.2.61 and later. When connecting to FX3UC- 32MT-LT(-2), function expansion board is required.
*4: When connecting to FX3UC, FX2NC-CNV-IF or FX3UC- 1PS-5V is required.
*5: FX3UC- 32MT-LT(-2): 7 units. FX3UC-**MT/D, FX3UC- **MT/DSS, FX3UC-16MR/D (S)-T: 8 units.
*6: FX3G 14 pt, 24 pt models: 1 board. 40 pt, 60 pt models: 2 boards.
*7: For connection to FX3S, FX3S-CNV-ADP is required.

 

Analog Input (A/D conversion)

Model
(Number of channels)
Input specifications Applicable FX PLC
Item Input voltage Input current FX
3S
FX
3G
FX
3U
FX
3GC
FX
3UC
FX3S-30MR/ES-2AD
FX3S-30MT/ES-2AD
FX3S-30MT/ESS-2AD
(Input 2ch)
Input
range
0 to 10 V DC
(Input resistance 115.7 kΩ)
- - - - - -
Resolution 10 mV
(10 V/1000)
-
FX2N-2AD
(Input 2 ch)
Input
range
0 to 10 V DC,
0 to 5 V DC
(Input resistance 200 kΩ)
The input characteristic is the same for each channel.
4 to 20 mA DC
(Input resistance 250 Ω)
The input characteristic is the same for each channel.
× ×
Max.
8 units
× *1*2

Max.
8 units
Resolution 2.5 mV
(10 V × 1/4000)
1.25 mV
(5 V × 1/4000)
4 μA
((20 - 4 mA) × 1/4000)
FX3U-4AD
(Input 4ch)
Input
range
-10 to 10 V DC
(Input resistance 200 kΩ)
-20 to 20 mA DC,
4 to 20 mA
(Input resistance 250 Ω)
× ×
Max.
8 units
× *1*2

Max.
8 units
Resolution 0.32 mV
(20 V × 1/64000)
1.25 μA
(40 mA × 1/32000)
FX3U-4AD-ADP
(Input 4ch)
Input
range
0 to 10 V DC
(Input resistance 194 kΩ)
4 to 20 mA DC
(Input resistance 250 Ω)
*8

Max.
1 unit
*4*3

Max.
2 units
*5

Max.
4 units

Max.
2 units
*5*6

Max.
4 units
Resolution 2.5 mV
(10 V/4000)
10 μA
(16 mA/1600)
FX3UC-4AD
(Input 4ch)
Input
range
-10 to 10 V DC
(Input resistance 200 kΩ)
4 to 20 mA DC,
-20 to 20 mA DC
(Input resistance 250 Ω)
× × × × *7*2

Max.
8 units
Resolution 0.32 mV
(20 V × 1/64000)
2.50 mV
(20 V × 1/8000)
1.25 μA
(40 mA × 1/32000)
5.0 μA
(40 mA × 1/8000)
FX2N-8AD
(Input 8 ch)
Input
range
-10 to 10 V DC
(Input resistance 200 kΩ)
4 to 20 mA DC
-20 to 20 mA DC
(Input resistance 250 Ω)
× ×
Max.
8 units
× *1*2

Max.
8 units
Resolution 0.63 mV
(20 V × 1/32000)
2.50 mV
(20 V × 1/8000)
2.5 μA
(40 mA × 1/16000)
2 μA
(16 mA × 1/8000)
5.0 μA
(40 mA × 1/8000)
4 μA
(16 mA × 1/4000)

 

*1: When connecting to FX3UC, FX2NC-CNV-IF or FX3UC- 1PS-5V is required.
*2: FX3UC- 32MT-LT(-2): 7 units. FX3UC-**MT/D, FX3UC- **MT/DSS, FX3UC-16MR/D (S)-T: 8 units.
*3: FX3G 14pt, 24pt models: 1 board. 40pt, 60pt models: 2 boards.
*4: When connecting to FX3G, FX3G-CNV-ADP is required.
*5: When connecting to FX3U, function expansion board is required.
*6: FX3UC- 32MT-LT supported from version 1.20 or later.
*7: FX3UC- 32MT-LT supported from version 1.30 or later.
*8: When connecting to FX3S, FX3S-CNV-ADP is required.

 

Analog Output (D/A conversion)

Model
(Number of channels)
Output specifications Applicable FX PLC
Item Output voltage Output current FX
3S
FX
3G
FX
3U
FX
3GC
FX
3UC
FX2N-2DA
(Output 2 ch)
Output
range
0 to 10 V DC,
0 to 5 V DC
(External load resistance value
2 kΩ to 1 MΩ)
4 to 20 mA DC
(External load resistance value
400 Ω or less)
× ×
Max.
8 units
× *1*2

Max.
8 units
Resolution 2.5 mV
(10 V × 1/4000)
1.25 mV
(5 V × 1/4000)
4 μA
((20 - 4) mA × 1/4000)
FX3U-4DA
(Output 4 ch)
Output
range
-10 to 10 V DC
(External load resistance value
1 kΩ to 1 MΩ)
0 to 20 mA DC
4 to 20 mA DC
(External load resistance value
500 Ωor less)
× ×
Max.
8 units
× *1*2

Max.
8 units
Resolution 0.32 mV
(20 V × 1/64000)
0.63 μA
(20 mA × 1/32000)
FX3U-4DA-ADP
(Output 4 ch)
Output
range
0 to 10 V DC
(External load resistance value
5 kΩ to 1 MΩ)
4 to 20 mA DC
(External load resistance value
500 Ω or less)
*7

Max.
1 unit
*3*4

Max.
2 units
*5

Max.
4 units

Max.
2 units
*5*6

Max.
4 units
Resolution 2.5 mV
(10 V/4000)
4 μA
(16 mA/4000)

 

*1: When connecting to FX3UC, FX2NC-CNV-IF or FX3UC- 1PS-5V is required.
*2: FX3UC- 32MT-LT(-2): 7 units. FX3UC-**MT/D, FX3UC- **MT/DSS, FX3UC-16MR/D (S)-T: 8 units.
*3: FX3G 14 pt, 24 pt models: 1 board. 40 pt, 60 pt models: 2 boards.
*4: When connecting to FX3G, FX3G-CNV-ADP is required.
*5: When connecting to FX3U, FX3UC-32MT-LT(-2), function expansion board is required.
*6: FX3UC- 32MT-LT supported from version 1.20 or later.
*7: When connecting to FX3S, FX3S-CNV-ADP is required.

 

  • Allen Bradley

Programmable Controllers

Allen Bradley control solutions set the standard — from the original programmable logic controller (PLC) invented in the 1970s to the technology embodied in the scalable, multi-disciplined and information-enabled programmable automation controller (PAC). Allen Bradley safety-certified controllers support your SIL 2 and SIL 3 application needs. Allen Bradley offer multiple controller types and sizes to fit your specific needs.


largecontrollerfamily front1 smprod
Large Control Systems

Allen Bradley Large Control Systems fit your most demanding application needs. They offer modular architectures and a range of I/O and network options. These powerful control solutions deliver world-class capabilities for all disciplines, from process to safety to motion. Designed for distributed or supervisory control applications, Allen Bradley large programmable automation controllers (PACs) and programmable logic controllers (PLC) provide exceptional reliability and performance.


smallcontrollerfamily front1 smprod

Small Control Systems 

The perfect solution for your mid-range applications, Allen Bradley small controllers offer the features and flexibility you need without the overhead of larger systems. Choose from standard and safety-certified controllers in chassis-based, packaged and modular designs. Typical applications include complex machine control, batch processing and building automation.


micronanocontrollerfamily front1 smprod

Micro & Nano Control Systems

Allen Bradley micro nano PLCs provide economical solutions to basic control needs for your simple machines ranging from relay replacement to simple control timing and logic. Compact packaging, integrated I/O and communication, and ease of use make these controllers an ideal choice for applications such as conveyor automation, security systems, and building and parking lot lighting.