• Address

    C-188, Sector 31-D, P&T Society,

    Korangi Industrial Area,

    Karachi-74900,

    Pakistan

     

  • Call us on

     +92-21-35070751

     +92-300-5776703

  • Mail us @

    info@pakplc.com

     

Analog expansion board (A/D conversion, D/A conversion)

Model
(Number of channels)
Input specifications Applicable FX PLC
Item Input voltage Input current FX
3S
FX
3G
FX
3U
FX
3GC
FX
3UC
FX3G-2AD-BD
(Input 2 ch)
Input
range
0 to 10 V DC
(Input resistance 198.7 kΩ)
4 to 20 mA DC
(Input resistance 250 Ω)
*3

Max.
1 unit
*1*2

Max.
2 units
× × ×
Resolution 2.5 mV
(10 V/4000)
8 μA
{(20 - 4 mA)/2000}
FX3G-1DA-BD
(Output 1 ch)
Output
range
0 to 10 V DC
(External load resistance value
2 kΩ to 1 MΩ)
4 to 20 mA DC
(External load resistance value
500 Ω or less)
*3

Max.
1 unit
*1*2

Max.
2 units
× × ×
Resolution 2.5 mV
(10 V/4000)
8 μA
{(20 - 4 mA)/2000}

*1: Supported by FX3G ver. 1.10 and later.
*2: FX3G 14pt, 24pt models: 1 board. 40pt, 60pt models: 2 boards.
*3: Function expansion board and FX3S-CNV-ADP cannot be used together.

 

Mixed Analog Input/Output (A/D conversion, D/A conversion)

Model
(Number of channels)
Input/output specifications Applicable FX PLC
Item Input/output voltage Input/output current FX
3S
FX
3G
FX
3U
FX
3GC
FX
3UC
FX3U-3A-ADP
(Input 2 ch)
(Output 1ch)
Input
range
0 to 10 V DC
(Input resistance
198.7 kΩ)
4 to 20 mA DC
(Input resistance 250 Ω)
*7

Max.
1 unit
*1*6

Max.
2 units
*2

Max.
4 units

Max.
2 units
*3

Max.
4 units
Output
range
0 to 10 V DC
(External load resistance value
5 kΩ to 1 MΩ)
4 to 20 mA DC
(External load resistance value
500 Ω or less)
Resolution [Input voltage]
2.5 mV (10 V/4000)
[Output voltage]
2.5 mV (10 V/4000)
[Input current]
5 μA (16 mA/3200)
[Onput current]
4 μA (16 mA/4000)
FX2N-5A
(Input 4 ch)
(Output 1ch)
Input
range
-100 to 100 mV DC
-10 to 10 V DC
(Input resistance 200 kΩ)
-20 to 20 mA DC
4 to 20 mA DC
(Input resistance 250 Ω)
× ×
Max.
8 units
× *4*5

Max.
8 units
Output
range
-10 to 10 V DC
(External load resistance value
2 kΩ to 1 MΩ)
0 to 20 mA DC,
4 to 20 mA DC
(External load resistance value
500 Ω or less)
Resolution 50 μV
(at ±100 mV)
312.5 μV
(at ±10 V)
1.25 μA,10 μA
((depending on
mode used))

 

*1: Supported by FX3G ver.1.20 and later. For connection to FX3G, FX3G-CNV-ADP is required.
*2: Supported by FX3U ver.2.61 and later. For connection to FX3U, function expansion board is required.
*3: Supported by FX3UC ver.2.61 and later. When connecting to FX3UC- 32MT-LT(-2), function expansion board is required.
*4: When connecting to FX3UC, FX2NC-CNV-IF or FX3UC- 1PS-5V is required.
*5: FX3UC- 32MT-LT(-2): 7 units. FX3UC-**MT/D, FX3UC- **MT/DSS, FX3UC-16MR/D (S)-T: 8 units.
*6: FX3G 14 pt, 24 pt models: 1 board. 40 pt, 60 pt models: 2 boards.
*7: For connection to FX3S, FX3S-CNV-ADP is required.

 

Analog Input (A/D conversion)

Model
(Number of channels)
Input specifications Applicable FX PLC
Item Input voltage Input current FX
3S
FX
3G
FX
3U
FX
3GC
FX
3UC
FX3S-30MR/ES-2AD
FX3S-30MT/ES-2AD
FX3S-30MT/ESS-2AD
(Input 2ch)
Input
range
0 to 10 V DC
(Input resistance 115.7 kΩ)
- - - - - -
Resolution 10 mV
(10 V/1000)
-
FX2N-2AD
(Input 2 ch)
Input
range
0 to 10 V DC,
0 to 5 V DC
(Input resistance 200 kΩ)
The input characteristic is the same for each channel.
4 to 20 mA DC
(Input resistance 250 Ω)
The input characteristic is the same for each channel.
× ×
Max.
8 units
× *1*2

Max.
8 units
Resolution 2.5 mV
(10 V × 1/4000)
1.25 mV
(5 V × 1/4000)
4 μA
((20 - 4 mA) × 1/4000)
FX3U-4AD
(Input 4ch)
Input
range
-10 to 10 V DC
(Input resistance 200 kΩ)
-20 to 20 mA DC,
4 to 20 mA
(Input resistance 250 Ω)
× ×
Max.
8 units
× *1*2

Max.
8 units
Resolution 0.32 mV
(20 V × 1/64000)
1.25 μA
(40 mA × 1/32000)
FX3U-4AD-ADP
(Input 4ch)
Input
range
0 to 10 V DC
(Input resistance 194 kΩ)
4 to 20 mA DC
(Input resistance 250 Ω)
*8

Max.
1 unit
*4*3

Max.
2 units
*5

Max.
4 units

Max.
2 units
*5*6

Max.
4 units
Resolution 2.5 mV
(10 V/4000)
10 μA
(16 mA/1600)
FX3UC-4AD
(Input 4ch)
Input
range
-10 to 10 V DC
(Input resistance 200 kΩ)
4 to 20 mA DC,
-20 to 20 mA DC
(Input resistance 250 Ω)
× × × × *7*2

Max.
8 units
Resolution 0.32 mV
(20 V × 1/64000)
2.50 mV
(20 V × 1/8000)
1.25 μA
(40 mA × 1/32000)
5.0 μA
(40 mA × 1/8000)
FX2N-8AD
(Input 8 ch)
Input
range
-10 to 10 V DC
(Input resistance 200 kΩ)
4 to 20 mA DC
-20 to 20 mA DC
(Input resistance 250 Ω)
× ×
Max.
8 units
× *1*2

Max.
8 units
Resolution 0.63 mV
(20 V × 1/32000)
2.50 mV
(20 V × 1/8000)
2.5 μA
(40 mA × 1/16000)
2 μA
(16 mA × 1/8000)
5.0 μA
(40 mA × 1/8000)
4 μA
(16 mA × 1/4000)

 

*1: When connecting to FX3UC, FX2NC-CNV-IF or FX3UC- 1PS-5V is required.
*2: FX3UC- 32MT-LT(-2): 7 units. FX3UC-**MT/D, FX3UC- **MT/DSS, FX3UC-16MR/D (S)-T: 8 units.
*3: FX3G 14pt, 24pt models: 1 board. 40pt, 60pt models: 2 boards.
*4: When connecting to FX3G, FX3G-CNV-ADP is required.
*5: When connecting to FX3U, function expansion board is required.
*6: FX3UC- 32MT-LT supported from version 1.20 or later.
*7: FX3UC- 32MT-LT supported from version 1.30 or later.
*8: When connecting to FX3S, FX3S-CNV-ADP is required.

 

Analog Output (D/A conversion)

Model
(Number of channels)
Output specifications Applicable FX PLC
Item Output voltage Output current FX
3S
FX
3G
FX
3U
FX
3GC
FX
3UC
FX2N-2DA
(Output 2 ch)
Output
range
0 to 10 V DC,
0 to 5 V DC
(External load resistance value
2 kΩ to 1 MΩ)
4 to 20 mA DC
(External load resistance value
400 Ω or less)
× ×
Max.
8 units
× *1*2

Max.
8 units
Resolution 2.5 mV
(10 V × 1/4000)
1.25 mV
(5 V × 1/4000)
4 μA
((20 - 4) mA × 1/4000)
FX3U-4DA
(Output 4 ch)
Output
range
-10 to 10 V DC
(External load resistance value
1 kΩ to 1 MΩ)
0 to 20 mA DC
4 to 20 mA DC
(External load resistance value
500 Ωor less)
× ×
Max.
8 units
× *1*2

Max.
8 units
Resolution 0.32 mV
(20 V × 1/64000)
0.63 μA
(20 mA × 1/32000)
FX3U-4DA-ADP
(Output 4 ch)
Output
range
0 to 10 V DC
(External load resistance value
5 kΩ to 1 MΩ)
4 to 20 mA DC
(External load resistance value
500 Ω or less)
*7

Max.
1 unit
*3*4

Max.
2 units
*5

Max.
4 units

Max.
2 units
*5*6

Max.
4 units
Resolution 2.5 mV
(10 V/4000)
4 μA
(16 mA/4000)

 

*1: When connecting to FX3UC, FX2NC-CNV-IF or FX3UC- 1PS-5V is required.
*2: FX3UC- 32MT-LT(-2): 7 units. FX3UC-**MT/D, FX3UC- **MT/DSS, FX3UC-16MR/D (S)-T: 8 units.
*3: FX3G 14 pt, 24 pt models: 1 board. 40 pt, 60 pt models: 2 boards.
*4: When connecting to FX3G, FX3G-CNV-ADP is required.
*5: When connecting to FX3U, FX3UC-32MT-LT(-2), function expansion board is required.
*6: FX3UC- 32MT-LT supported from version 1.20 or later.
*7: When connecting to FX3S, FX3S-CNV-ADP is required.

 

  • Omron

Omron

CP1E

Compact and cost-effective

The CP1E delivers an exceptional solution for automating small and compact machines, and is part of Omron’s Lean Automation concept. Lean Automation fits into stand-alone machines or modules within a larger machine. Its merit lies in its simplicity, compactness and economically attractive solutions.  

  • 6 high-speed counter inputs and 2 high speed pulse outputs
  • Instruction set upwards compatible with CP1H, CJ1, and CS1
  • Optional RS232C and RS-422/485 serial ports for N-type application model
  • Simple motion functions including Modbus-RTU simple master
          Features  | Lineup |  Specifications